Filtered by vendor Siemens
Subscribe
Total
2079 CVE
| CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
|---|---|---|---|---|---|
| CVE-2022-43724 | 1 Siemens | 2 Sicam Pas, Sicam Pqs | 2025-04-22 | N/A | 9.8 CRITICAL |
| A vulnerability has been identified in SICAM PAS/PQS (All versions < V7.0). Affected software transmits the database credentials for the inbuilt SQL server in cleartext. In combination with the by default enabled xp_cmdshell feature unauthenticated remote attackers could execute custom OS commands. At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. | |||||
| CVE-2022-43723 | 1 Siemens | 2 Sicam Pas, Sicam Pqs | 2025-04-22 | N/A | 7.5 HIGH |
| A vulnerability has been identified in SICAM PAS/PQS (All versions < V7.0), SICAM PAS/PQS (All versions >= 7.0 < V8.06). Affected software does not properly validate the input for a certain parameter in the s7ontcp.dll. This could allow an unauthenticated remote attacker to send messages and create a denial of service condition as the application crashes. At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. | |||||
| CVE-2022-43722 | 1 Siemens | 2 Sicam Pas, Sicam Pqs | 2025-04-22 | N/A | 7.8 HIGH |
| A vulnerability has been identified in SICAM PAS/PQS (All versions < V7.0). Affected software does not properly secure a folder containing library files. This could allow an attacker to place a custom malicious DLL in this folder which is then run with SYSTEM rights when a service is started that requires this DLL. At the time of assigning the CVE, the affected firmware version of the component has already been superseded by succeeding mainline versions. | |||||
| CVE-2022-46355 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 7.5 HIGH |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). The affected products are vulnerable to an "Exposure of Sensitive Information to an Unauthorized Actor" vulnerability by leaking sensitive data in the HTTP Referer. | |||||
| CVE-2022-46354 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 5.3 MEDIUM |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). The webserver of an affected device is missing specific security headers. This could allow an remote attacker to extract confidential session information under certain circumstances. | |||||
| CVE-2022-45936 | 1 Siemens | 1 Mendix Email Connector | 2025-04-22 | N/A | 8.1 HIGH |
| A vulnerability has been identified in Mendix Email Connector (All versions < V2.0.0). Affected versions of the module improperly handle access control for some module entities. This could allow authenticated remote attackers to read and manipulate sensitive information. | |||||
| CVE-2022-44575 | 1 Siemens | 1 Plm Help Server | 2025-04-22 | N/A | 6.1 MEDIUM |
| A vulnerability has been identified in PLM Help Server V4.2 (All versions). A reflected cross-site scripting (XSS) vulnerability exists in the web interface of the affected application that could allow an attacker to execute malicious javascript code by tricking users into accessing a malicious link. | |||||
| CVE-2022-46353 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 9.8 CRITICAL |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). The webserver of affected devices calculates session ids and nonces in an insecure manner. This could allow an unauthenticated remote attacker to brute-force session ids and hijack existing sessions. | |||||
| CVE-2022-46352 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 7.5 HIGH |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products. | |||||
| CVE-2022-46351 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 5.5 MEDIUM |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). Specially crafted PROFINET DCP packets could cause a denial of service condition of affected products on a local Ethernet segment (Layer 2). | |||||
| CVE-2022-46350 | 1 Siemens | 10 6gk5204-0ba00-2kb2, 6gk5204-0ba00-2kb2 Firmware, 6gk5204-0ba00-2mb2 and 7 more | 2025-04-22 | N/A | 6.1 MEDIUM |
| A vulnerability has been identified in SCALANCE X204RNA (HSR) (All versions < V3.2.7), SCALANCE X204RNA (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (HSR) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP) (All versions < V3.2.7), SCALANCE X204RNA EEC (PRP/HSR) (All versions < V3.2.7). The integrated web server could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into accessing a malicious link. This can be used by an attacker to trigger a malicious request on the affected device. | |||||
| CVE-2017-6869 | 1 Siemens | 1 Viewport For Web Office Portal | 2025-04-20 | 10.0 HIGH | 9.8 CRITICAL |
| A vulnerability was discovered in Siemens ViewPort for Web Office Portal before revision number 1453 that could allow an unauthenticated remote user to upload arbitrary code and execute it with the permissions of the operating-system user running the web server by sending specially crafted network packets to port 443/TCP or port 80/TCP. | |||||
| CVE-2017-2684 | 1 Siemens | 1 Simatic Logon | 2025-04-20 | 6.8 MEDIUM | 9.0 CRITICAL |
| Siemens SIMATIC Logon prior to V1.5 SP3 Update 2 could allow an attacker with knowledge of a valid user name, and physical or network access to the affected system, to bypass the application-level authentication. | |||||
| CVE-2017-2685 | 1 Siemens | 3 Sinumerik Integrate Access Mymachine\/ethernet, Sinumerik Integrate Operate Client, Sinumerik Operate | 2025-04-20 | 5.8 MEDIUM | 7.4 HIGH |
| Siemens SINUMERIK Integrate Operate Clients between 2.0.3.00.016 (including) and 2.0.6 (excluding) and between 3.0.4.00.032 (including) and 3.0.6 (excluding) contain a vulnerability that could allow an attacker to read and manipulate data in TLS sessions while performing a man-in-the-middle (MITM) attack. | |||||
| CVE-2016-8566 | 1 Siemens | 1 Sicam Pas | 2025-04-20 | 4.6 MEDIUM | 7.8 HIGH |
| An issue was discovered in Siemens SICAM PAS before 8.00. Because of Storing Passwords in a Recoverable Format, an authenticated local attacker with certain privileges could possibly reconstruct the passwords of users for accessing the database. | |||||
| CVE-2017-12735 | 1 Siemens | 2 Logo\!, Logo\! 8 Bm Firmware | 2025-04-20 | 5.8 MEDIUM | 7.4 HIGH |
| A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). An attacker who performs a Man-in-the-Middle attack between the LOGO! BM and other devices could potentially decrypt and modify network traffic. | |||||
| CVE-2017-2681 | 1 Siemens | 155 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 Pn Io and 152 more | 2025-04-20 | 6.1 MEDIUM | 6.5 MEDIUM |
| Specially crafted PROFINET DCP packets sent on a local Ethernet segment (Layer 2) to an affected product could cause a denial of service condition of that product. Human interaction is required to recover the system. PROFIBUS interfaces are not affected. | |||||
| CVE-2017-12741 | 1 Siemens | 76 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200p and 73 more | 2025-04-20 | 7.8 HIGH | 7.5 HIGH |
| Specially crafted packets sent to port 161/udp could cause a denial of service condition. The affected devices must be restarted manually. | |||||
| CVE-2017-9944 | 1 Siemens | 2 7kt Pac1200 Data Manager, 7kt Pac1200 Data Manager Firmware | 2025-04-20 | 10.0 HIGH | 9.8 CRITICAL |
| A vulnerability has been identified in Siemens 7KT PAC1200 data manager (7KT1260) in all versions < V2.03. The integrated web server (port 80/tcp) of the affected devices could allow an unauthenticated remote attacker to perform administrative operations over the network. | |||||
| CVE-2017-2689 | 1 Siemens | 1 Ruggedcom Rox I | 2025-04-20 | 6.5 MEDIUM | 8.8 HIGH |
| Siemens RUGGEDCOM ROX I (all versions) allow an authenticated user to bypass access restrictions in the web interface at port 10000/TCP to obtain privileged file system access or change configuration settings. | |||||