CVE-2022-34755 | 1 Schneider-electric | 1 Easergy Builder Installer | 2024-11-21 | N/A | 6.3 MEDIUM |
A CWE-427 - Uncontrolled Search Path Element vulnerability exists that could allow an attacker with a local privileged account to place a specially crafted file on the target machine, which may give the attacker the ability to execute arbitrary code during the installation process initiated by a valid user. Affected Products: Easergy Builder Installer (1.7.23 and prior) | |||||
CVE-2022-34754 | 1 Schneider-electric | 4 Acti9 Powertag Link C \(a9xelc10-a\), Acti9 Powertag Link C \(a9xelc10-a\) Firmware, Acti9 Powertag Link C \(a9xelc10-b\) and 1 more | 2024-11-21 | N/A | 6.8 MEDIUM |
A CWE-269: Improper Privilege Management vulnerability exists that could allow elevated functionality when guessing credentials. Affected Products: Acti9 PowerTag Link C (A9XELC10-A) (V1.7.5 and prior), Acti9 PowerTag Link C (A9XELC10-B) (V2.12.0 and prior) | |||||
CVE-2022-34753 | 1 Schneider-electric | 2 Spacelogic C-bus Home Controller, Spacelogic C-bus Home Controller Firmware | 2024-11-21 | N/A | 8.8 HIGH |
A CWE-78: Improper Neutralization of Special Elements used in an OS Command ('OS Command Injection') vulnerability exists that could cause remote root exploit when the command is compromised. Affected Products: SpaceLogic C-Bus Home Controller (5200WHC2), formerly known as C-Bus Wiser Homer Controller MK2 (V1.31.460 and prior) | |||||
CVE-2022-32530 | 1 Schneider-electric | 1 Geo Scada Mobile | 2024-11-21 | 6.8 MEDIUM | 4.8 MEDIUM |
A CWE-668 Exposure of Resource to Wrong Sphere vulnerability exists that could cause users to be misled, hiding alarms, showing the wrong server connection option or the wrong control request when a mobile device has been compromised by a malicious application. Affected Product: Geo SCADA Mobile (Build 222 and prior) | |||||
CVE-2022-32528 | 1 Schneider-electric | 1 Interactive Graphical Scada System | 2024-11-21 | N/A | 8.6 HIGH |
A CWE-306: Missing Authentication for Critical Function vulnerability exists that could cause access to manipulate and read specific files in the IGSS project report directory, potentially leading to a denial-of-service condition when an attacker sends specific messages. Affected Products: IGSS Data Server - IGSSdataServer.exe (Versions prior to V15.0.0.22170) | |||||
CVE-2022-30238 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 7.5 HIGH | 8.3 HIGH |
A CWE-287: Improper Authentication vulnerability exists that could allow an attacker to take over the admin account when an attacker hijacks a session. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30237 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 5.0 MEDIUM | 8.2 HIGH |
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists that could allow authentication credentials to be recovered when an attacker breaks the encoding. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30236 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 6.4 MEDIUM | 8.2 HIGH |
A CWE-669: Incorrect Resource Transfer Between Spheres vulnerability exists that could allow unauthorized access when an attacker uses cross-domain attacks. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30235 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 5.0 MEDIUM | 8.6 HIGH |
A CWE-307: Improper Restriction of Excessive Authentication Attempts vulnerability exists that could allow unauthorized access when an attacker uses brute force. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30234 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 10.0 HIGH | 9.4 CRITICAL |
A CWE-798: Use of Hard-coded Credentials vulnerability exists that could allow arbitrary code to be executed when root level access is obtained. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30233 | 1 Schneider-electric | 4 Wiser Smart Eer21000, Wiser Smart Eer21000 Firmware, Wiser Smart Eer21001 and 1 more | 2024-11-21 | 4.3 MEDIUM | 6.5 MEDIUM |
A CWE-20: Improper Input Validation vulnerability exists that could allow the product to be maliciously manipulated when the user is tricked into performing certain actions on a webpage. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-30232 | 1 Schneider-electric | 2 Powerlogic Ion Setup, Powerlogic Ion Setup Firmware | 2024-11-21 | 6.5 MEDIUM | 8.0 HIGH |
A CWE-20: Improper Input Validation vulnerability exists that could cause potential remote code execution when an attacker is able to intercept and modify a request on the same network or has configuration access to an ION device on the network. Affected Products: Wiser Smart, EER21000 & EER21001 (V4.5 and prior) | |||||
CVE-2022-26507 | 2 Att, Schneider-electric | 9 Xmill, Ecostruxure Control Expert, Ecostruxure Process Expert and 6 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
** UNSUPPORTED WHEN ASSIGNED ** A heap-based buffer overflow exists in XML Decompression DecodeTreeBlock in AT&T Labs Xmill 0.7. A crafted input file can lead to remote code execution. This is not the same as any of: CVE-2021-21810, CVE-2021-21811, CVE-2021-21812, CVE-2021-21815, CVE-2021-21825, CVE-2021-21826, CVE-2021-21828, CVE-2021-21829, or CVE-2021-21830. NOTE: This vulnerability only affects products that are no longer supported by the maintainer. | |||||
CVE-2022-24323 | 1 Schneider-electric | 2 Ecostruxure Control Expert, Ecostruxure Process Expert | 2024-11-21 | 4.3 MEDIUM | 5.3 MEDIUM |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software, when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Process Expert (V2021 and prior), EcoStruxure Control Expert (V15.0 SP1 and prior) | |||||
CVE-2022-24322 | 1 Schneider-electric | 1 Ecostruxure Control Expert | 2024-11-21 | 4.3 MEDIUM | 5.3 MEDIUM |
A CWE-119: Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists that could cause a disruption of communication between the Modicon controller and the engineering software when an attacker is able to intercept and manipulate specific Modbus response data. Affected Product: EcoStruxure Control Expert (V15.0 SP1 and prior) | |||||
CVE-2022-24321 | 1 Schneider-electric | 3 Clearscada, Ecostruxure Geo Scada Expert 2019, Ecostruxure Geo Scada Expert 2020 | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-754: Improper Check for Unusual or Exceptional Conditions vulnerability exists that could cause Denial of Service against the Geo SCADA server when receiving a malformed HTTP request. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions) | |||||
CVE-2022-24320 | 1 Schneider-electric | 3 Clearscada, Ecostruxure Geo Scada Expert 2019, Ecostruxure Geo Scada Expert 2020 | 2024-11-21 | 4.3 MEDIUM | 5.9 MEDIUM |
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA database server are intercepted. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions) | |||||
CVE-2022-24319 | 1 Schneider-electric | 3 Clearscada, Ecostruxure Geo Scada Expert 2019, Ecostruxure Geo Scada Expert 2020 | 2024-11-21 | 4.3 MEDIUM | 5.9 MEDIUM |
A CWE-295: Improper Certificate Validation vulnerability exists that could allow a Man-in-theMiddle attack when communications between the client and Geo SCADA web server are intercepted. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions) | |||||
CVE-2022-24318 | 1 Schneider-electric | 3 Clearscada, Ecostruxure Geo Scada Expert 2019, Ecostruxure Geo Scada Expert 2020 | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-326: Inadequate Encryption Strength vulnerability exists that could cause non-encrypted communication with the server when outdated versions of the ViewX client are used. Affected Product: ClearSCADA (All Versions), EcoStruxure Geo SCADA Expert 2019 (All Versions), EcoStruxure Geo SCADA Expert 2020 (All Versions) | |||||
CVE-2022-24317 | 1 Schneider-electric | 1 Interactive Graphical Scada System Data Server | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A CWE-862: Missing Authorization vulnerability exists that could cause information exposure when an attacker sends a specific message. Affected Product: Interactive Graphical SCADA System Data Server (V15.0.0.22020 and prior) |