Filtered by vendor Schneider-electric
Subscribe
Total
719 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2012-1990 | 1 Schneider-electric | 2 Kerweb, Kerwin | 2024-11-21 | 4.3 MEDIUM | N/A |
Multiple cross-site scripting (XSS) vulnerabilities in Schneider Electric Kerweb before 3.0.1 and Kerwin before 6.0.1 allow remote attackers to inject arbitrary web script or HTML via (1) the evtvariablename parameter in an evts.xml action to kw.dll, (2) unspecified search fields, or (3) unspecified content-display fields. | |||||
CVE-2012-0931 | 1 Schneider-electric | 1 Modicon Quantum Plc | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
Schneider Electric Modicon Quantum PLC does not perform authentication between the Unity software and PLC, which allows remote attackers to cause a denial of service or possibly execute arbitrary code via unspecified vectors. | |||||
CVE-2012-0930 | 1 Schneider-electric | 1 Modicon Quantum Plc | 2024-11-21 | 4.3 MEDIUM | 6.1 MEDIUM |
Cross-site scripting (XSS) vulnerability in Schneider Electric Modicon Quantum PLC allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
CVE-2012-0929 | 1 Schneider-electric | 1 Modicon Quantum Plc | 2024-11-21 | 7.8 HIGH | 7.5 HIGH |
Multiple buffer overflows in Schneider Electric Modicon Quantum PLC allow remote attackers to cause a denial of service via malformed requests to the (1) FTP server or (2) HTTP server. | |||||
CVE-2011-5163 | 2 Mitsubishi-automation, Schneider-electric | 2 Mx4 Scada, Citectscada | 2024-11-21 | 4.6 MEDIUM | N/A |
Buffer overflow in an unspecified third-party component in the Batch module for Schneider Electric CitectSCADA before 7.20 and Mitsubishi MX4 SCADA before 7.20 allows local users to execute arbitrary code via a long string in a login sequence. | |||||
CVE-2011-4861 | 1 Schneider-electric | 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 | 2024-11-21 | 10.0 HIGH | N/A |
The modbus_125_handler function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) allows remote attackers to install arbitrary firmware updates via a MODBUS 125 function code to TCP port 502. | |||||
CVE-2011-4860 | 1 Schneider-electric | 3 Quantum Ethernet Module 140noe77100, Quantum Ethernet Module 140noe77101, Quantum Ethernet Module 140noe77111 | 2024-11-21 | 10.0 HIGH | N/A |
The ComputePassword function in the Schneider Electric Quantum Ethernet Module on the NOE 771 device (aka the Quantum 140NOE771* module) generates the password for the fwupgrade account by performing a calculation on the MAC address, which makes it easier for remote attackers to obtain access via a (1) ARP request message or (2) Neighbor Solicitation message. | |||||
CVE-2011-4859 | 1 Schneider-electric | 21 M340 Ethernet Module Bmxnoe0100, M340 Ethernet Module Bmxnoe0110, M340 Ethernet Module Bmxp342020 and 18 more | 2024-11-21 | 10.0 HIGH | N/A |
The Schneider Electric Quantum Ethernet Module, as used in the Quantum 140NOE771* and 140CPU65* modules, the Premium TSXETY* and TSXP57* modules, the M340 BMXNOE01* and BMXP3420* modules, and the STB DIO STBNIC2212 and STBNIP2* modules, uses hardcoded passwords for the (1) AUTCSE, (2) AUT_CSE, (3) fdrusers, (4) ftpuser, (5) loader, (6) nic2212, (7) nimrohs2212, (8) nip2212, (9) noe77111_v500, (10) ntpupdate, (11) pcfactory, (12) sysdiag, (13) target, (14) test, (15) USER, and (16) webserver accounts, which makes it easier for remote attackers to obtain access via the (a) TELNET, (b) Windriver Debug, or (c) FTP port. | |||||
CVE-2011-4036 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2024-11-21 | 5.0 MEDIUM | N/A |
Directory traversal vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to read arbitrary files via unspecified vectors. | |||||
CVE-2011-4035 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2024-11-21 | 4.3 MEDIUM | N/A |
Cross-site scripting (XSS) vulnerability in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
CVE-2011-4034 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2024-11-21 | 9.3 HIGH | N/A |
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to execute arbitrary code or cause a denial of service via unspecified vectors. | |||||
CVE-2011-4033 | 1 Schneider-electric | 3 Citecthistorian, Citectscada Reports, Vijeo Historian | 2024-11-21 | 4.3 MEDIUM | N/A |
Buffer overflow in the Steema TeeChart ActiveX control, as used in Schneider Electric Vijeo Historian 4.30 and earlier, CitectHistorian 4.30 and earlier, and CitectSCADAReports 4.10 and earlier, allows remote attackers to cause a denial of service via unspecified vectors. | |||||
CVE-2011-3330 | 1 Schneider-electric | 6 Monitor Pro, Opc Factory Server, Pl7 Pro and 3 more | 2024-11-21 | 7.2 HIGH | N/A |
Buffer overflow in the UnitelWay Windows Device Driver, as used in Schneider Electric Unity Pro 6 and earlier, OPC Factory Server 3.34, Vijeo Citect 7.20 and earlier, Telemecanique Driver Pack 2.6 and earlier, Monitor Pro 7.6 and earlier, and PL7 Pro 4.5 and earlier, allows local users, and possibly remote attackers, to execute arbitrary code via an unspecified system parameter. | |||||
CVE-2011-3144 | 2 Aveva, Schneider-electric | 3 Clearscada, Scx 67, Scx 68 | 2024-11-21 | 4.3 MEDIUM | N/A |
Cross-site scripting (XSS) vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
CVE-2011-3143 | 2 Aveva, Schneider-electric | 3 Clearscada, Scx 67, Scx 68 | 2024-11-21 | 10.0 HIGH | N/A |
Use-after-free vulnerability in Control Microsystems ClearSCADA 2005, 2007, and 2009 before R2.3 and R1.4, as used in SCX before 67 R4.5 and 68 R3.9, allows remote attackers to cause a denial of service (crash) and possibly execute arbitrary code via unspecified long strings that trigger heap memory corruption. | |||||
CVE-2024-10575 | 1 Schneider-electric | 1 Ecostruxure It Gateway | 2024-11-19 | N/A | 9.8 CRITICAL |
CWE-862: Missing Authorization vulnerability exists that could cause unauthorized access when enabled on the network and potentially impacting connected devices. | |||||
CVE-2024-9409 | 1 Schneider-electric | 6 Powerlogic Pm5320, Powerlogic Pm5320 Firmware, Powerlogic Pm5340 and 3 more | 2024-11-19 | N/A | 7.5 HIGH |
CWE-400: An Uncontrolled Resource Consumption vulnerability exists that could cause the device to become unresponsive resulting in communication loss when a large amount of IGMP packets is present in the network. | |||||
CVE-2024-8422 | 1 Schneider-electric | 1 Zelio Soft 2 | 2024-10-16 | N/A | 7.8 HIGH |
CWE-416: Use After Free vulnerability exists that could cause arbitrary code execution, denial of service and loss of confidentiality & integrity when application user opens a malicious Zelio Soft 2 project file. | |||||
CVE-2024-8306 | 1 Schneider-electric | 2 Vijeo Designer, Vijeo Designer Embedded In Ecostruxure Machine Expert | 2024-09-18 | N/A | 7.8 HIGH |
CWE-269: Improper Privilege Management vulnerability exists that could cause unauthorized access, loss of confidentiality, integrity and availability of the workstation when non-admin authenticated user tries to perform privilege escalation by tampering with the binaries. |