Total
5 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2019-10936 | 1 Siemens | 130 Dk Standard Ethernet Controller, Dk Standard Ethernet Controller Firmware, Ek-ertec 200 and 127 more | 2024-07-09 | 5.0 MEDIUM | 7.5 HIGH |
Affected devices improperly handle large amounts of specially crafted UDP packets. This could allow an unauthenticated remote attacker to trigger a denial of service condition. | |||||
CVE-2021-3449 | 11 Checkpoint, Debian, Fedoraproject and 8 more | 163 Multi-domain Management, Multi-domain Management Firmware, Quantum Security Gateway and 160 more | 2024-06-21 | 4.3 MEDIUM | 5.9 MEDIUM |
An OpenSSL TLS server may crash if sent a maliciously crafted renegotiation ClientHello message from a client. If a TLSv1.2 renegotiation ClientHello omits the signature_algorithms extension (where it was present in the initial ClientHello), but includes a signature_algorithms_cert extension then a NULL pointer dereference will result, leading to a crash and a denial of service attack. A server is only vulnerable if it has TLSv1.2 and renegotiation enabled (which is the default configuration). OpenSSL TLS clients are not impacted by this issue. All OpenSSL 1.1.1 versions are affected by this issue. Users of these versions should upgrade to OpenSSL 1.1.1k. OpenSSL 1.0.2 is not impacted by this issue. Fixed in OpenSSL 1.1.1k (Affected 1.1.1-1.1.1j). | |||||
CVE-2022-40227 | 1 Siemens | 20 Simatic Hmi Comfort Panels, Simatic Hmi Comfort Panels Firmware, Simatic Hmi Ktp1200 Basic and 17 more | 2024-02-04 | N/A | 7.5 HIGH |
A vulnerability has been identified in SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions < V17 Update 4), SIMATIC HMI KTP Mobile Panels (All versions < V17 Update 4), SIMATIC HMI KTP1200 Basic (All versions < V17 Update 5), SIMATIC HMI KTP400 Basic (All versions < V17 Update 5), SIMATIC HMI KTP700 Basic (All versions < V17 Update 5), SIMATIC HMI KTP900 Basic (All versions < V17 Update 5), SIPLUS HMI KTP1200 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP400 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP700 BASIC (All versions < V17 Update 5), SIPLUS HMI KTP900 BASIC (All versions < V17 Update 5). Affected devices do not properly validate input sent to certain services over TCP. This could allow an unauthenticated remote attacker to cause a permanent denial of service condition (requiring a device reboot) by sending specially crafted TCP packets. | |||||
CVE-2019-19276 | 1 Siemens | 4 Simatic Hmi Comfort Panels, Simatic Hmi Comfort Panels Firmware, Simatic Hmi Ktp Mobile Panels and 1 more | 2024-02-04 | 5.0 MEDIUM | 5.3 MEDIUM |
A vulnerability has been identified in SIMATIC HMI Comfort Panels 1st Generation (incl. SIPLUS variants) (All versions < V16 Update 4), SIMATIC HMI KTP Mobile Panels (All versions < V16 Update 4). Specially crafted packets sent to port 161/udp can cause the SNMP service of affected devices to crash. A manual restart of the device is required to resume operation of the service. | |||||
CVE-2020-15798 | 1 Siemens | 20 Simatic Hmi Comfort Panels, Simatic Hmi Comfort Panels Firmware, Simatic Hmi Ktp Mobile Panels and 17 more | 2024-02-04 | 9.3 HIGH | 9.8 CRITICAL |
A vulnerability has been identified in SIMATIC HMI Comfort Panels (incl. SIPLUS variants) (All versions < V16 Update 3a), SIMATIC HMI KTP Mobile Panels (All versions < V16 Update 3a), SINAMICS GH150 (All versions), SINAMICS GL150 (with option X30) (All versions), SINAMICS GM150 (with option X30) (All versions), SINAMICS SH150 (All versions), SINAMICS SL150 (All versions), SINAMICS SM120 (All versions), SINAMICS SM150 (All versions), SINAMICS SM150i (All versions). Affected devices with enabled telnet service do not require authentication for this service. This could allow a remote attacker to gain full access to the device. (ZDI-CAN-12046) |