Vulnerabilities (CVE)

Filtered by vendor Siemens Subscribe
Total 1885 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2017-5711 3 Asus, Intel, Siemens 394 B150-a, B150-a Firmware, B150-plus and 391 more 2025-04-20 7.2 HIGH 7.8 HIGH
Multiple buffer overflows in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allow attacker with local access to the system to execute arbitrary code with AMT execution privilege.
CVE-2017-9946 1 Siemens 8 Apogee Pxc, Apogee Pxc Firmware, Apogee Pxc Modular and 5 more 2025-04-20 5.0 MEDIUM 7.5 HIGH
A vulnerability has been identified in Siemens APOGEE PXC and TALON TC BACnet Automation Controllers in all versions <V3.5. An attacker with network access to the integrated web server (80/tcp and 443/tcp) could bypass the authentication and download sensitive information from the device.
CVE-2017-14491 13 Arista, Arubanetworks, Canonical and 10 more 29 Eos, Arubaos, Ubuntu Linux and 26 more 2025-04-20 7.5 HIGH 9.8 CRITICAL
Heap-based buffer overflow in dnsmasq before 2.78 allows remote attackers to cause a denial of service (crash) or execute arbitrary code via a crafted DNS response.
CVE-2017-12069 2 Ocpfoundation, Siemens 4 Local Discovery Server, Ua .net, Simatic Pcs7 and 1 more 2025-04-20 6.4 MEDIUM 8.2 HIGH
An XXE vulnerability has been identified in OPC Foundation UA .NET Sample Code before 2017-03-21 and Local Discovery Server (LDS) before 1.03.367. Among the affected products are Siemens SIMATIC PCS7 (All versions V8.1 and earlier), SIMATIC WinCC (All versions < V7.4 SP1), SIMATIC WinCC Runtime Professional (All versions < V14 SP1), SIMATIC NET PC Software, and SIMATIC IT Production Suite. By sending specially crafted packets to the OPC Discovery Server at port 4840/tcp, an attacker might cause the system to access various resources chosen by the attacker.
CVE-2017-5712 3 Asus, Intel, Siemens 394 B150-a, B150-a Firmware, B150-plus and 391 more 2025-04-20 9.0 HIGH 7.2 HIGH
Buffer overflow in Active Management Technology (AMT) in Intel Manageability Engine Firmware 8.x/9.x/10.x/11.0/11.5/11.6/11.7/11.10/11.20 allows attacker with remote Admin access to the system to execute arbitrary code with AMT execution privilege.
CVE-2017-6867 1 Siemens 3 Simatic Wincc, Simatic Wincc \(tia Portal\), Simatic Wincc Runtime 2025-04-20 4.0 MEDIUM 4.9 MEDIUM
A vulnerability was discovered in Siemens SIMATIC WinCC (V7.3 before Upd 11 and V7.4 before SP1), SIMATIC WinCC Runtime Professional (V13 before SP2 and V14 before SP1), SIMATIC WinCC (TIA Portal) Professional (V13 before SP2 and V14 before SP1) that could allow an authenticated, remote attacker who is member of the "administrators" group to crash services by sending specially crafted messages to the DCOM interface.
CVE-2017-2683 1 Siemens 1 Ruggedcom Network Management Software 2025-04-20 4.3 MEDIUM 8.2 HIGH
A non-privileged user of the Siemens web application RUGGEDCOM NMS < V1.2 on port 8080/TCP and 8081/TCP could perform a persistent Cross-Site Scripting (XSS) attack, potentially resulting in obtaining administrative permissions.
CVE-2017-5689 3 Hpe, Intel, Siemens 71 Proliant Ml10 Gen9 Server, Proliant Ml10 Gen9 Server Firmware, Active Management Technology Firmware and 68 more 2025-04-20 10.0 HIGH 9.8 CRITICAL
An unprivileged network attacker could gain system privileges to provisioned Intel manageability SKUs: Intel Active Management Technology (AMT) and Intel Standard Manageability (ISM). An unprivileged local attacker could provision manageability features gaining unprivileged network or local system privileges on Intel manageability SKUs: Intel Active Management Technology (AMT), Intel Standard Manageability (ISM), and Intel Small Business Technology (SBT).
CVE-2017-9938 1 Siemens 1 Simatic Logon 2025-04-20 5.0 MEDIUM 7.5 HIGH
A vulnerability was discovered in Siemens SIMATIC Logon (All versions before V1.6) that could allow specially crafted packets sent to the SIMATIC Logon Remote Access service on port 16389/tcp to cause a Denial-of-Service condition. The service restarts automatically.
CVE-2017-12736 1 Siemens 15 Ruggedcom, Ruggedcom Ros, Ruggedcom Rsl910 and 12 more 2025-04-20 5.8 MEDIUM 8.8 HIGH
A vulnerability has been identified in RUGGEDCOM ROS for RSL910 devices (All versions < ROS V5.0.1), RUGGEDCOM ROS for all other devices (All versions < ROS V4.3.4), SCALANCE XB-200/XC-200/XP-200/XR300-WG (All versions between V3.0 (including) and V3.0.2 (excluding)), SCALANCE XR-500/XM-400 (All versions between V6.1 (including) and V6.1.1 (excluding)). After initial configuration, the Ruggedcom Discovery Protocol (RCDP) is still able to writeto the device under certain conditions, potentially allowing users located in the adjacentnetwork of the targeted device to perform unauthorized administrative actions.
CVE-2017-2686 1 Siemens 1 Ruggedcom Rox I 2025-04-20 4.0 MEDIUM 6.5 MEDIUM
Siemens RUGGEDCOM ROX I (all versions) contain a vulnerability that could allow an authenticated user to read arbitrary files through the web interface at port 10000/TCP and access sensitive information.
CVE-2017-9945 1 Siemens 2 7km Pac Switched Ethernet Profinet Expansion Module, 7km Pac Switched Ethernet Profinet Expansion Module Firmware 2025-04-20 6.1 MEDIUM 6.5 MEDIUM
In the Siemens 7KM PAC Switched Ethernet PROFINET expansion module (All versions < V2.1.3), a Denial-of-Service condition could be induced by a specially crafted PROFINET DCP packet sent as a local Ethernet (Layer 2) broadcast. The affected component requires a manual restart via the main device to recover.
CVE-2017-6866 1 Siemens 1 Xhq Server 2025-04-20 4.0 MEDIUM 6.5 MEDIUM
A vulnerability was discovered in Siemens XHQ server 4 and 5 (4 before V4.7.1.3 and 5 before V5.0.0.2) that could allow an authenticated low-privileged remote user to gain read access to data in the XHQ solution exceeding his configured permission level.
CVE-2017-14023 1 Siemens 2 Simatic Pcs7, Simatic Wincc 2025-04-20 4.0 MEDIUM 4.9 MEDIUM
An Improper Input Validation issue was discovered in Siemens SIMATIC PCS 7 V8.1 prior to V8.1 SP1 with WinCC V7.3 Upd 13, and V8.2 all versions. The improper input validation vulnerability has been identified, which may allow an authenticated remote attacker who is a member of the administrators group to crash services by sending specially crafted messages to the DCOM interface.
CVE-2017-9939 1 Siemens 1 Sipass Integrated 2025-04-20 7.5 HIGH 9.8 CRITICAL
A vulnerability was discovered in Siemens SiPass integrated (All versions before V2.70) that could allow an attacker with network access to the SiPass integrated server to bypass the authentication mechanism and perform administrative operations.
CVE-2017-6871 1 Siemens 2 Simatic Wincc Sm\@rtclient, Simatic Wincc Sm\@rtclient Lite 2025-04-20 4.6 MEDIUM 5.4 MEDIUM
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2) and SIMATIC WinCC Sm@rtClient for Android Lite (All versions before V1.0.2.2). An attacker with physical access to an unlocked mobile device, that has the affected app running, could bypass the app's authentication mechanism under certain conditions.
CVE-2017-6870 1 Siemens 1 Simatic Wincc Sm\@rtclient 2025-04-20 5.8 MEDIUM 7.4 HIGH
A vulnerability was discovered in Siemens SIMATIC WinCC Sm@rtClient for Android (All versions before V1.0.2.2). The existing TLS protocol implementation could allow an attacker to read and modify data within a TLS session while performing a Man-in-the-Middle (MitM) attack.
CVE-2017-2688 1 Siemens 1 Ruggedcom Rox I 2025-04-20 6.8 MEDIUM 8.8 HIGH
The integrated web server in Siemens RUGGEDCOM ROX I (all versions) at port 10000/TCP could allow remote attackers to perform actions with the privileges of an authenticated user, provided the targeted user has an active session and is induced into clicking on a malicious link or into visiting a malicious website, aka CSRF.
CVE-2016-7987 1 Siemens 8 Eta2 Firmware, Eta4 Firmware, Sicam Ak and 5 more 2025-04-20 7.8 HIGH 7.5 HIGH
An issue was discovered in Siemens ETA4 firmware (all versions prior to Revision 08) of the SM-2558 extension module for: SICAM AK, SICAM TM 1703, SICAM BC 1703, and SICAM AK 3. Specially crafted packets sent to Port 2404/TCP could cause the affected device to go into defect mode. A cold start might be required to recover the system, a Denial-of-Service Vulnerability.
CVE-2017-12738 1 Siemens 2 Sm-2556, Sm-2556 Firmware 2025-04-20 4.3 MEDIUM 6.1 MEDIUM
An issue was discovered on Siemens SICAM RTUs SM-2556 COM Modules with the firmware variants ENOS00, ERAC00, ETA2, ETLS00, MODi00, and DNPi00. The integrated web server (port 80/tcp) of the affected devices could allow Cross-Site Scripting (XSS) attacks if unsuspecting users are tricked into clicking on a malicious link.