Filtered by vendor Mitsubishielectric
Subscribe
Total
151 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2021-20601 | 1 Mitsubishielectric | 99 Got2000 Gt2103-pmbd, Got2000 Gt2103-pmbd Firmware, Got2000 Gt2103-pmbds and 96 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Improper input validation vulnerability in GOT2000 series GT27 model all versions, GOT2000 series GT25 model all versions, GOT2000 series GT23 model all versions, GOT2000 series GT21 model all versions, GOT SIMPLE series GS21 model all versions, and GT SoftGOT2000 all versions allows an remote unauthenticated attacker to write a value that exceeds the configured input range limit by sending a malicious packet to rewrite the device value. As a result, the system operation may be affected, such as malfunction. | |||||
CVE-2022-23130 | 2 Iconics, Mitsubishielectric | 3 Genesis64, Hyper Historian, Mc Works64 | 2024-02-04 | 4.3 MEDIUM | 5.5 MEDIUM |
Buffer Over-read vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.97 and prior and ICONICS Hyper Historian versions 10.97 and prior allows an attacker to cause a DoS condition in the database server by getting a legitimate user to import a configuration file containing specially crafted stored procedures into GENESIS64 or MC Works64 and execute commands against the database from GENESIS64 or MC Works64. | |||||
CVE-2021-20608 | 1 Mitsubishielectric | 1 Gx Works2 | 2024-02-04 | 5.0 MEDIUM | 7.5 HIGH |
Improper Handling of Length Parameter Inconsistency vulnerability in Mitsubishi Electric GX Works2 versions 1.606G and prior allows a remote unauthenticated attacker to cause a DoS condition in GX Works2 by getting GX Works2 to read a tampered program file from a Mitsubishi Electric PLC by sending malicious crafted packets to tamper with the program file. | |||||
CVE-2021-20600 | 1 Mitsubishielectric | 2 R12ccpu-v, R12ccpu-v Firmware | 2024-02-04 | 7.1 HIGH | 5.9 MEDIUM |
Uncontrolled resource consumption in Mitsubishi Electric MELSEC iQ-R series C Controller Module R12CCPU-V Firmware Versions "16" and prior allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition by sending a large number of packets in a short time while the module starting up. System reset is required for recovery. | |||||
CVE-2021-20612 | 1 Mitsubishielectric | 6 Fx3u-enet, Fx3u-enet-l, Fx3u-enet-l Firmware and 3 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Lack of administrator control over security vulnerability in MELSEC-F series FX3U-ENET Firmware version 1.14 and prior, FX3U-ENET-L Firmware version 1.14 and prior and FX3U-ENET-P502 Firmware version 1.14 and prior allows a remote unauthenticated attacker to cause a denial-of-service (DoS) condition in communication function of the product or other unspecified effects by sending specially crafted packets to an unnecessary opening of TCP port. Control by MELSEC-F series PLC is not affected by this vulnerability, but system reset is required for recovery. | |||||
CVE-2021-20606 | 1 Mitsubishielectric | 3 Ezsocket, Gx Works2, Melsoft Navigator | 2024-02-04 | 4.3 MEDIUM | 5.5 MEDIUM |
Out-of-bounds Read vulnerability in Mitsubishi Electric GX Works2 versions 1.606G and prior, Mitsubishi Electric MELSOFT Navigator versions 2.84N and prior and Mitsubishi Electric EZSocket versions 5.4 and prior allows an attacker to cause a DoS condition in the software by getting a user to open malicious project file specially crafted by an attacker. | |||||
CVE-2022-23128 | 2 Iconics, Mitsubishielectric | 5 Analytix, Genesis64, Hyper Historian and 2 more | 2024-02-04 | 7.5 HIGH | 9.8 CRITICAL |
Incomplete List of Disallowed Inputs vulnerability in Mitsubishi Electric MC Works64 versions 4.00A (10.95.201.23) to 4.04E (10.95.210.01), ICONICS GENESIS64 versions 10.95.3 to 10.97, ICONICS Hyper Historian versions 10.95.3 to 10.97, ICONICS AnalytiX versions 10.95.3 to 10.97 and ICONICS MobileHMI versions 10.95.3 to 10.97 allows a remote unauthenticated attacker to bypass the authentication of MC Works64, GENESIS64, Hyper Historian, AnalytiX and MobileHMI, and gain unauthorized access to the products, by sending specially crafted WebSocket packets to FrameWorX server, one of the functions of the products. | |||||
CVE-2022-23127 | 2 Iconics, Mitsubishielectric | 2 Mobilehmi, Mc Works64 | 2024-02-04 | 4.3 MEDIUM | 6.1 MEDIUM |
Cross-site Scripting vulnerability in Mitsubishi Electric MC Works64 versions 4.04E (10.95.210.01) and prior and ICONICS MobileHMI versions 10.96.2 and prior allows a remote unauthenticated attacker to gain authentication information of an MC Works64 or MobileHMI and perform any operation using the acquired authentication information, by injecting a malicious script in the URL of a monitoring screen delivered from the MC Works64 server or MobileHMI server to an application for mobile devices and leading a legitimate user to access this URL. | |||||
CVE-2021-20590 | 1 Mitsubishielectric | 12 Got2000 Gt25, Got2000 Gt25 Firmware, Got2000 Gt27 and 9 more | 2024-02-04 | 4.3 MEDIUM | 7.5 HIGH |
Improper authentication vulnerability in GOT2000 series GT27 model VNC server versions 01.39.010 and prior, GOT2000 series GT25 model VNC server versions 01.39.010 and prior, GOT2000 series GT21 model GT2107-WTBD VNC server versions 01.40.000 and prior, GOT2000 series GT21 model GT2107-WTSD VNC server versions 01.40.000 and prior, GOT SIMPLE series GS21 model GS2110-WTBD-N VNC server versions 01.40.000 and prior and GOT SIMPLE series GS21 model GS2107-WTBD-N VNC server versions 01.40.000 and prior allows a remote unauthenticated attacker to gain unauthorized access via specially crafted packets when the "VNC server" function is used. | |||||
CVE-2021-27041 | 3 Autodesk, Iconics, Mitsubishielectric | 13 Advance Steel, Autocad, Autocad Architecture and 10 more | 2024-02-04 | 6.8 MEDIUM | 7.8 HIGH |
A maliciously crafted DWG file can be used to write beyond the allocated buffer while parsing DWG files. This vulnerability can be exploited to execute arbitrary code | |||||
CVE-2021-20596 | 1 Mitsubishielectric | 3 Fx3u-enet-l Firmware, Fx3u-enet-p502 Firmware, Fx3u-enet Firmware | 2024-02-04 | 5.0 MEDIUM | 7.5 HIGH |
NULL Pointer Dereference in MELSEC-F Series FX3U-ENET firmware version 1.14 and prior, FX3U-ENET-L firmware version 1.14 and prior and FX3U-ENET-P502 firmware version 1.14 and prior allows a remote unauthenticated attacker to cause a DoS condition in communication by sending specially crafted packets. Control by MELSEC-F series PLC is not affected and system reset is required for recovery. | |||||
CVE-2021-20591 | 1 Mitsubishielectric | 40 R00cpu, R00cpu Firmware, R01cpu and 37 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Uncontrolled Resource Consumption vulnerability in Mitsubishi Electric MELSEC iQ-R series CPU modules (R00/01/02CPU all versions, R04/08/16/32/120(EN)CPU all versions, R08/16/32/120SFCPU all versions, R08/16/32/120PCPU all versions, R08/16/32/120PSFCPU all versions) allows a remote unauthenticated attacker to prevent legitimate clients from connecting to the MELSOFT transmission port (TCP/IP) by not closing a connection properly, which may lead to a denial of service (DoS) condition. | |||||
CVE-2021-27040 | 3 Autodesk, Iconics, Mitsubishielectric | 13 Advance Steel, Autocad, Autocad Architecture and 10 more | 2024-02-04 | 4.3 MEDIUM | 3.3 LOW |
A maliciously crafted DWG file can be forced to read beyond allocated boundaries when parsing the DWG file. This vulnerability can be exploited to execute arbitrary code. | |||||
CVE-2021-20598 | 1 Mitsubishielectric | 16 R08psfcpu, R08psfcpu Firmware, R08sfcpu and 13 more | 2024-02-04 | 5.0 MEDIUM | 5.3 MEDIUM |
Overly Restrictive Account Lockout Mechanism vulnerability in Mitsubishi Electric MELSEC iQ-R series CPU modules (R08/16/32/120SFCPU all versions, R08/16/32/120PSFCPU all versions) allows a remote unauthenticated attacker to lockout a legitimate user by continuously trying login with incorrect password. | |||||
CVE-2021-20592 | 1 Mitsubishielectric | 7 Got2000 Gt23, Got2000 Gt23 Firmware, Got2000 Gt25 and 4 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Missing synchronization vulnerability in GOT2000 series GT27 model communication driver versions 01.19.000 through 01.39.010, GT25 model communication driver versions 01.19.000 through 01.39.010 and GT23 model communication driver versions 01.19.000 through 01.39.010 and GT SoftGOT2000 versions 1.170C through 1.256S allows a remote unauthenticated attacker to cause DoS condition on the MODBUS/TCP slave communication function of the products by rapidly and repeatedly connecting and disconnecting to and from the MODBUS/TCP communication port on a target. Restart or reset is required to recover. | |||||
CVE-2020-5657 | 1 Mitsubishielectric | 10 Melsec Iq-rd81dl96, Melsec Iq-rd81dl96 Firmware, Melsec Iq-rd81mes96n and 7 more | 2024-02-04 | 3.3 LOW | 6.5 MEDIUM |
Improper neutralization of argument delimiters in a command ('Argument Injection') vulnerability in TCP/IP function included in the firmware of MELSEC iQ-R series (RJ71EIP91 EtherNet/IP Network Interface Module First 2 digits of serial number are '02' or before, RJ71PN92 PROFINET IO Controller Module First 2 digits of serial number are '01' or before, RD81DL96 High Speed Data Logger Module First 2 digits of serial number are '08' or before, RD81MES96N MES Interface Module First 2 digits of serial number are '04' or before, and RD81OPC96 OPC UA Server Module First 2 digits of serial number are '04' or before) allows unauthenticated attackers on adjacent network to stop the network functions of the products via a specially crafted packet. | |||||
CVE-2020-5646 | 1 Mitsubishielectric | 6 Coreos, Gt1450-qlbde, Gt1450-qmbde and 3 more | 2024-02-04 | 5.0 MEDIUM | 7.5 HIGH |
NULL pointer dereferences vulnerability in TCP/IP function included in the firmware of GT14 Model of GOT 1000 series (GT1455-QTBDE CoreOS version "05.65.00.BD" and earlier, GT1450-QMBDE CoreOS version "05.65.00.BD" and earlier, GT1450-QLBDE CoreOS version "05.65.00.BD" and earlier, GT1455HS-QTBDE CoreOS version "05.65.00.BD" and earlier, and GT1450HS-QMBDE CoreOS version "05.65.00.BD" and earlier) allows a remote unauthenticated attacker to stop the network functions of the products via a specially crafted packet. | |||||
CVE-2020-5668 | 1 Mitsubishielectric | 56 R00cpu, R00cpu Firmware, R01cpu and 53 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Uncontrolled resource consumption vulnerability in MELSEC iQ-R Series modules (R00/01/02CPU firmware version '19' and earlier, R04/08/16/32/120 (EN) CPU firmware version '51' and earlier, R08/16/32/120SFCPU firmware version '22' and earlier, R08/16/32/120PCPU firmware version '25' and earlier, R08/16/32/120PSFCPU firmware version '06' and earlier, RJ71EN71 firmware version '47' and earlier, RJ71GF11-T2 firmware version '47' and earlier, RJ72GF15-T2 firmware version '07' and earlier, RJ71GP21-SX firmware version '47' and earlier, RJ71GP21S-SX firmware version '47' and earlier, and RJ71GN11-T2 firmware version '11' and earlier) allows a remote unauthenticated attacker to cause an error in a CPU unit and cause a denial-of-service (DoS) condition in execution of the program and its communication, or to cause a denial-of-service (DoS) condition in communication via the unit by receiving a specially crafted SLMP packet | |||||
CVE-2020-5647 | 1 Mitsubishielectric | 6 Coreos, Gt1450-qlbde, Gt1450-qmbde and 3 more | 2024-02-04 | 7.5 HIGH | 9.8 CRITICAL |
Improper access control vulnerability in TCP/IP function included in the firmware of GT14 Model of GOT 1000 series (GT1455-QTBDE CoreOS version ’05.65.00.BD’ and earlier, GT1450-QMBDE CoreOS version ’05.65.00.BD’ and earlier, GT1450-QLBDE CoreOS version ’05.65.00.BD’ and earlier, GT1455HS-QTBDE CoreOS version ’05.65.00.BD’ and earlier, and GT1450HS-QMBDE CoreOS version ’05.65.00.BD’ and earlier) allows a remote unauthenticated attacker to stop the network functions of the products or execute a malicious program via a specially crafted packet. | |||||
CVE-2020-16850 | 1 Mitsubishielectric | 38 R00cpu, R00cpu Firmware, R01cpu and 35 more | 2024-02-04 | 7.8 HIGH | 7.5 HIGH |
Mitsubishi MELSEC iQ-R Series PLCs with firmware 49 allow an unauthenticated attacker to halt the industrial process by sending a crafted packet over the network. This denial of service attack exposes Improper Input Validation. After halting, physical access to the PLC is required in order to restore production, and the device state is lost. This is related to R04CPU, RJ71GF11-T2, R04CPU, and RJ71GF11-T2. |