Filtered by vendor Siemens
Subscribe
Total
1885 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2015-5698 | 1 Siemens | 2 Simatic S7 1200 Cpu, Simatic S7 1200 Cpu Firmware | 2025-04-12 | 7.5 HIGH | N/A |
Cross-site request forgery (CSRF) vulnerability in the web server on Siemens SIMATIC S7-1200 CPU devices with firmware before 4.1.3 allows remote attackers to hijack the authentication of unspecified victims via unknown vectors. | |||||
CVE-2016-4784 | 1 Siemens | 9 Siprotec 4 En100, Siprotec Compact Model 7rw80, Siprotec Compact Model 7sd80 and 6 more | 2025-04-12 | 5.0 MEDIUM | 5.3 MEDIUM |
A vulnerability has been identified in firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02; SIPROTEC 7SJ686 : All versions < V 4.83; SIPROTEC 7UT686 : All versions < V 4.01; SIPROTEC 7SD686 : All versions < V 4.03; SIPROTEC 7SJ66 : All versions < V 4.20. The integrated web server (port 80/tcp) of the affected devices could allow remote attackers to obtain sensitive device information if network access was obtained. | |||||
CVE-2015-8214 | 1 Siemens | 8 Simatic Cp 343-1, Simatic Cp 343-1 Firmware, Simatic Cp 443-1 and 5 more | 2025-04-12 | 9.7 HIGH | N/A |
A vulnerability has been identified in SIMATIC NET CP 342-5 (incl. SIPLUS variants) (All versions), SIMATIC NET CP 343-1 Advanced (incl. SIPLUS variants) (All versions < V3.0.44), SIMATIC NET CP 343-1 Lean (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 343-1 Standard (incl. SIPLUS variants) (All versions < V3.1.1), SIMATIC NET CP 443-1 Advanced (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-1 Standard (incl. SIPLUS variants) (All versions < V3.2.9), SIMATIC NET CP 443-5 Basic (incl. SIPLUS variants) (All versions), SIMATIC NET CP 443-5 Extended (All versions), TIM 3V-IE / TIM 3V-IE Advanced (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 3V-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0), TIM 4R-IE (incl. SIPLUS NET variants) (All versions < V2.6.0), TIM 4R-IE DNP3 (incl. SIPLUS NET variants) (All versions < V3.1.0). The implemented access protection level enforcement of the affected communication processors (CP) could possibly allow unauthenticated users to perform administrative operations on the CPs if network access (port 102/TCP) is available and the CPs' configuration was stored on their corresponding CPUs. | |||||
CVE-2015-1601 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | 6.8 MEDIUM | N/A |
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 allows man-in-the-middle attackers to obtain sensitive information or modify transmitted data via unspecified vectors. | |||||
CVE-2014-4684 | 1 Siemens | 2 Simatic Pcs7, Wincc | 2025-04-12 | 6.0 MEDIUM | N/A |
The database server in Siemens SIMATIC WinCC before 7.3, as used in PCS7 and other products, allows remote authenticated users to gain privileges via a request to TCP port 1433. | |||||
CVE-2014-2733 | 1 Siemens | 1 Sinema Server | 2025-04-12 | 5.0 MEDIUM | N/A |
Siemens SINEMA Server before 12 SP1 allows remote attackers to cause a denial of service (web-interface outage) via crafted HTTP requests to port (1) 4999 or (2) 80. | |||||
CVE-2014-2731 | 1 Siemens | 1 Sinema Server | 2025-04-12 | 9.3 HIGH | N/A |
Multiple unspecified vulnerabilities in the integrated web server in Siemens SINEMA Server before 12 SP1 allow remote attackers to execute arbitrary code via HTTP traffic to port (1) 4999 or (2) 80. | |||||
CVE-2015-1597 | 1 Siemens | 1 Spcanywhere | 2025-04-12 | 6.8 MEDIUM | N/A |
The Siemens SPCanywhere application for Android does not use encryption during the loading of code, which allows man-in-the-middle attackers to execute arbitrary code by modifying the client-server data stream. | |||||
CVE-2014-5074 | 1 Siemens | 8 Simatic S7-1500 Cpu Firmware, Simatic S7-1511-1 Pn Cpu, Simatic S7-1513-1 Pn Cpu and 5 more | 2025-04-12 | 7.1 HIGH | N/A |
Siemens SIMATIC S7-1500 CPU devices with firmware before 1.6 allow remote attackers to cause a denial of service (device restart and STOP transition) via crafted TCP packets. | |||||
CVE-2016-3963 | 1 Siemens | 1 Scalance S613 | 2025-04-12 | 5.0 MEDIUM | 5.3 MEDIUM |
Siemens SCALANCE S613 allows remote attackers to cause a denial of service (web-server outage) via traffic to TCP port 443. | |||||
CVE-2016-4956 | 6 Novell, Ntp, Opensuse and 3 more | 11 Suse Manager, Ntp, Leap and 8 more | 2025-04-12 | 5.0 MEDIUM | 5.3 MEDIUM |
ntpd in NTP 4.x before 4.2.8p8 allows remote attackers to cause a denial of service (interleaved-mode transition and time change) via a spoofed broadcast packet. NOTE: this vulnerability exists because of an incomplete fix for CVE-2016-1548. | |||||
CVE-2015-1602 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | 2.1 LOW | N/A |
Siemens SIMATIC STEP 7 (TIA Portal) 12 and 13 before 13 SP1 Upd1 improperly stores password data within project files, which makes it easier for local users to determine cleartext (1) protection-level passwords or (2) web-server passwords by leveraging the ability to read these files. | |||||
CVE-2014-2257 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | 7.8 HIGH | N/A |
Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allow remote attackers to cause a denial of service (defect-mode transition) via crafted ISO-TSAP packets. | |||||
CVE-2014-5231 | 2 Apple, Siemens | 2 Iphone Os, Simatic Wincc Sm\@rtclient | 2025-04-12 | 2.1 LOW | N/A |
The Siemens SIMATIC WinCC Sm@rtClient app before 1.0.2 for iOS allows physically proximate attackers to extract the password from storage via unspecified vectors. | |||||
CVE-2014-2250 | 1 Siemens | 6 Simatic S7 Cpu-1211c, Simatic S7 Cpu 1200 Firmware, Simatic S7 Cpu 1212c and 3 more | 2025-04-12 | 8.3 HIGH | N/A |
The random-number generator on Siemens SIMATIC S7-1200 CPU PLC devices with firmware before 4.0 does not have sufficient entropy, which makes it easier for remote attackers to defeat cryptographic protection mechanisms and hijack sessions via unspecified vectors, a different vulnerability than CVE-2014-2251. | |||||
CVE-2014-2246 | 1 Siemens | 1 Simatic S7-1500 Cpu Firmware | 2025-04-12 | 4.3 MEDIUM | N/A |
Cross-site scripting (XSS) vulnerability in the integrated web server on Siemens SIMATIC S7-1500 CPU PLC devices with firmware before 1.5.0 allows remote attackers to inject arbitrary web script or HTML via unspecified vectors. | |||||
CVE-2015-1598 | 1 Siemens | 1 Spcanywhere | 2025-04-12 | 2.1 LOW | N/A |
The Siemens SPCanywhere application for Android does not properly store application passwords, which allows physically proximate attackers to obtain sensitive information by examining the device filesystem. | |||||
CVE-2016-9159 | 1 Siemens | 21 Simatic S7-300 Cpu 312, Simatic S7-300 Cpu 314, Simatic S7-300 Cpu 315-2 Dp and 18 more | 2025-04-12 | 4.3 MEDIUM | 5.9 MEDIUM |
A vulnerability has been identified in SIMATIC S7-300 CPU family (All versions), SIMATIC S7-300 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 PN/DP V7 CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 V6 and earlier CPU family (All versions), SIMATIC S7-400 V7 CPU family (All versions), SIMATIC S7-410 V8 CPU family (All versions), SIMATIC S7-410 V8 CPU family (incl. SIPLUS variants) (All versions). An attacker with network access to port 102/tcp (ISO-TSAP) or via Profibus could obtain credentials from the PLC if protection-level 2 is configured on the affected devices. | |||||
CVE-2015-1356 | 1 Siemens | 1 Simatic Step 7 | 2025-04-12 | 4.4 MEDIUM | N/A |
Siemens SIMATIC STEP 7 (TIA Portal) before 13 SP1 determines a user's privileges on the basis of project-file fields that lack integrity protection, which allows remote attackers to establish arbitrary authorization data via a modified file. | |||||
CVE-2014-8479 | 1 Siemens | 9 Scalance X-300, Scalance X-300 Series Firmware, Scalance X-300eec and 6 more | 2025-04-12 | 6.8 MEDIUM | N/A |
The FTP server on Siemens SCALANCE X-300 switches with firmware before 4.0 and SCALANCE X 408 switches with firmware before 4.0 allows remote authenticated users to cause a denial of service (reboot) via crafted FTP packets. |