Filtered by vendor Hitachienergy
Subscribe
Total
70 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2024-41156 | 1 Hitachienergy | 6 Tro610, Tro610 Firmware, Tro620 and 3 more | 2024-10-31 | N/A | 4.3 MEDIUM |
Profile files from TRO600 series radios are extracted in plain-text and encrypted file formats. Profile files provide potential attackers valuable configuration information about the Tropos network. Profiles can only be exported by authenticated users with write access. | |||||
CVE-2024-41153 | 1 Hitachienergy | 6 Tro610, Tro610 Firmware, Tro620 and 3 more | 2024-10-31 | N/A | 7.2 HIGH |
Command injection vulnerability in the Edge Computing UI for the TRO600 series radios that allows for the execution of arbitrary system commands. If exploited, an attacker with write access to the web UI can execute commands on the device with root privileges, far more extensive than what the write privilege intends. | |||||
CVE-2024-3980 | 1 Hitachienergy | 2 Microscada Pro Sys600, Microscada X Sys600 | 2024-10-30 | N/A | 8.8 HIGH |
The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the application. | |||||
CVE-2024-3982 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-10-30 | N/A | 8.2 HIGH |
An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level is not enabled and only users with administrator rights can enable it. | |||||
CVE-2024-4872 | 1 Hitachienergy | 2 Microscada Pro Sys600, Microscada X Sys600 | 2024-10-30 | N/A | 8.8 HIGH |
A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential. | |||||
CVE-2024-7941 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-10-30 | N/A | 4.3 MEDIUM |
An HTTP parameter may contain a URL value and could cause the web application to redirect the request to the specified URL. By modifying the URL value to a malicious site, an attacker may successfully launch a phishing scam and steal user credentials. | |||||
CVE-2024-28022 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-10-30 | N/A | 6.5 MEDIUM |
A vulnerability exists in the UNEM server / APIGateway that if exploited allows a malicious user to perform an arbitrary number of authentication attempts using different passwords, and eventually gain access to other components in the same security realm using the targeted account. | |||||
CVE-2024-28020 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-10-30 | N/A | 8.0 HIGH |
A user/password reuse vulnerability exists in the FOXMAN-UN/UNEM application and server management. If exploited a malicious high-privileged user could use the passwords and login information through complex routines to extend access on the server and other services. | |||||
CVE-2024-28024 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-10-29 | N/A | 4.1 MEDIUM |
A vulnerability exists in the FOXMAN-UN/UNEM in which sensitive information is stored in cleartext within a resource that might be accessible to another control sphere. | |||||
CVE-2024-28021 | 1 Hitachienergy | 3 Foxman-un, Foxman Un, Unem | 2024-10-29 | N/A | 7.4 HIGH |
A vulnerability exists in the FOXMAN-UN/UNEM server that affects the message queueing mechanism’s certificate validation. If exploited an attacker could spoof a trusted entity causing a loss of confidentiality and integrity. | |||||
CVE-2022-2277 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-09-25 | N/A | 7.5 HIGH |
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | |||||
CVE-2022-1778 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-09-25 | N/A | 4.4 MEDIUM |
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | |||||
CVE-2023-6711 | 1 Hitachienergy | 2 Rtu500, Rtu500 Firmware | 2024-09-25 | N/A | 7.5 HIGH |
Vulnerability exists in SCI IEC 60870-5-104 and HCI IEC 60870-5-104 that affects the RTU500 series product versions listed below. Specially crafted messages sent to the mentioned components are not validated properly and can result in buffer overflow and as final consequence to a reboot of an RTU500 CMU. | |||||
CVE-2022-28613 | 2 Abb, Hitachienergy | 3 Rtu500 Firmware, Rtu500, Rtu500 Firmware | 2024-09-25 | 7.8 HIGH | 7.5 HIGH |
A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function. | |||||
CVE-2023-4518 | 1 Hitachienergy | 6 Relion 650, Relion 650 Firmware, Relion 670 and 3 more | 2024-09-23 | N/A | 7.5 HIGH |
A vulnerability exists in the input validation of the GOOSE messages where out of range values received and processed by the IED caused a reboot of the device. In order for an attacker to exploit the vulnerability, goose receiving blocks need to be configured. | |||||
CVE-2024-7940 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-08-28 | N/A | 9.8 CRITICAL |
The product exposes a service that is intended for local only to all network interfaces without any authentication. | |||||
CVE-2024-2011 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-08-15 | N/A | 9.8 CRITICAL |
A heap-based buffer overflow vulnerability exists in the FOXMAN-UN/UNEM that if exploited will generally lead to a denial of service but can be used to execute arbitrary code, which is usually outside the scope of a program's implicit security policy | |||||
CVE-2024-2012 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-08-15 | N/A | 9.8 CRITICAL |
vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway that if exploited an attacker could use to allow unintended commands or code to be executed on the UNEM server allowing sensitive data to be read or modified or could cause other unintended behavior | |||||
CVE-2024-2013 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-08-15 | N/A | 10.0 CRITICAL |
An authentication bypass vulnerability exists in the FOXMAN-UN/UNEM server / API Gateway component that if exploited allows attackers without any access to interact with the services and the post-authentication attack surface. | |||||
CVE-2023-1711 | 1 Hitachienergy | 2 Foxman-un, Unem | 2024-07-25 | N/A | 4.4 MEDIUM |
A vulnerability exists in a FOXMAN-UN and UNEM logging component, it only affects systems that use remote authentication to the network elements. If exploited an attacker could obtain confidential information. List of CPEs: * cpe:2.3:a:hitachienergy:foxman_un:R9C:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R10C:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R11A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R11B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R14A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R14B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R15A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R15B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy:foxman_un:R16A:*:*:*:*:*:*:* * * cpe:2.3:a:hitachienergy:unem:R9C:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R10C:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R11A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R11B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R14A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R14B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R15A:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R15B:*:*:*:*:*:*:* * cpe:2.3:a:hitachienergy: unem :R16A:*:*:*:*:*:*:* |