Total
8 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2024-3980 | 1 Hitachienergy | 2 Microscada Pro Sys600, Microscada X Sys600 | 2024-10-30 | N/A | 8.8 HIGH |
The MicroSCADA Pro/X SYS600 product allows an authenticated user input to control or influence paths or file names that are used in filesystem operations. If exploited the vulnerability allows the attacker to access or modify system files or other files that are critical to the application. | |||||
CVE-2024-3982 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-10-30 | N/A | 8.2 HIGH |
An attacker with local access to machine where MicroSCADA X SYS600 is installed, could enable the session logging supporting the product and try to exploit a session hijacking of an already established session. By default, the session logging level is not enabled and only users with administrator rights can enable it. | |||||
CVE-2024-4872 | 1 Hitachienergy | 2 Microscada Pro Sys600, Microscada X Sys600 | 2024-10-30 | N/A | 8.8 HIGH |
A vulnerability exists in the query validation of the MicroSCADA Pro/X SYS600 product. If exploited this could allow an authenticated attacker to inject code towards persistent data. Note that to successfully exploit this vulnerability an attacker must have a valid credential. | |||||
CVE-2024-7941 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-10-30 | N/A | 4.3 MEDIUM |
An HTTP parameter may contain a URL value and could cause the web application to redirect the request to the specified URL. By modifying the URL value to a malicious site, an attacker may successfully launch a phishing scam and steal user credentials. | |||||
CVE-2022-2277 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-09-25 | N/A | 7.5 HIGH |
Improper Input Validation vulnerability exists in the Hitachi Energy MicroSCADA X SYS600's ICCP stack during the ICCP communication establishment causes a denial-of-service when ICCP of SYS600 is request to forward any data item updates with timestamps too distant in the future to any remote ICCP system. By default, ICCP is not configured and not enabled. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10.2 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | |||||
CVE-2022-1778 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-09-25 | N/A | 4.4 MEDIUM |
Improper Input Validation vulnerability in Hitachi Energy MicroSCADA X SYS600 while reading a specific configuration file causes a buffer-overflow that causes a failure to start the SYS600. The configuration file can only be accessed by an administrator access. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* | |||||
CVE-2024-7940 | 1 Hitachienergy | 1 Microscada X Sys600 | 2024-08-28 | N/A | 9.8 CRITICAL |
The product exposes a service that is intended for local only to all network interfaces without any authentication. | |||||
CVE-2022-29490 | 1 Hitachienergy | 2 Microscada X Sys600, Sys600 | 2024-02-04 | N/A | 8.8 HIGH |
Improper Authorization vulnerability exists in the Workplace X WebUI of the Hitachi Energy MicroSCADA X SYS600 allows an authenticated user to execute any MicroSCADA internal scripts irrespective of the authenticated user's role. This issue affects: Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:* |