Filtered by vendor Rockwellautomation
Subscribe
Total
296 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2020-27267 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 6.4 MEDIUM | 9.1 CRITICAL |
KEPServerEX v6.0 to v6.9, ThingWorx Kepware Server v6.8 and v6.9, ThingWorx Industrial Connectivity (all versions), OPC-Aggregator (all versions), Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server v7.68.804 and v7.66, and Software Toolbox TOP Server all 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data. | |||||
CVE-2020-27265 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions are vulnerable to a stack-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and remotely execute code. | |||||
CVE-2020-27263 | 4 Ge, Ptc, Rockwellautomation and 1 more | 7 Industrial Gateway Server, Kepware Kepserverex, Opc-aggregator and 4 more | 2024-11-21 | 6.4 MEDIUM | 9.1 CRITICAL |
KEPServerEX: v6.0 to v6.9, ThingWorx Kepware Server: v6.8 and v6.9, ThingWorx Industrial Connectivity: All versions, OPC-Aggregator: All versions, Rockwell Automation KEPServer Enterprise, GE Digital Industrial Gateway Server: v7.68.804 and v7.66, Software Toolbox TOP Server: All 6.x versions, are vulnerable to a heap-based buffer overflow. Opening a specifically crafted OPC UA message could allow an attacker to crash the server and potentially leak data. | |||||
CVE-2020-27255 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious set attribute requests, which could result in the leaking of sensitive information. This information disclosure could lead to the bypass of address space layout randomization (ASLR). | |||||
CVE-2020-27253 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.8 HIGH | 7.5 HIGH |
A flaw exists in the Ingress/Egress checks routine of FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to specifically craft a malicious packet resulting in a denial-of-service condition on the device. | |||||
CVE-2020-27251 | 1 Rockwellautomation | 1 Factorytalk Linx | 2024-11-21 | 7.5 HIGH | 9.8 CRITICAL |
A heap overflow vulnerability exists within FactoryTalk Linx Version 6.11 and prior. This vulnerability could allow a remote, unauthenticated attacker to send malicious port ranges, which could result in remote code execution. | |||||
CVE-2020-25184 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2024-11-21 | 2.1 LOW | 7.8 HIGH |
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x stores the password in plaintext in a file that is in the same directory as the executable file. ISaGRAF Runtime reads the file and saves the data in a variable without any additional modification. A local, unauthenticated attacker could compromise the user passwords, resulting in information disclosure. | |||||
CVE-2020-25182 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2024-11-21 | 4.6 MEDIUM | 6.7 MEDIUM |
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x searches for and loads DLLs as dynamic libraries. Uncontrolled loading of dynamic libraries could allow a local, unauthenticated attacker to execute arbitrary code. This vulnerability only affects ISaGRAF Runtime when running on Microsoft Windows systems. | |||||
CVE-2020-25180 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2024-11-21 | 4.3 MEDIUM | 5.3 MEDIUM |
Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x includes the functionality of setting a password that is required to execute privileged commands. The password value passed to ISaGRAF Runtime is the result of encryption performed with a fixed key value using the tiny encryption algorithm (TEA) on an entered or saved password. A remote, unauthenticated attacker could pass their own encrypted password to the ISaGRAF 5 Runtime, which may result in information disclosure on the device. | |||||
CVE-2020-25178 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2024-11-21 | 9.3 HIGH | 7.5 HIGH |
ISaGRAF Workbench communicates with Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x using TCP/IP. This communication protocol provides various file system operations, as well as the uploading of applications. Data is transferred over this protocol unencrypted, which could allow a remote unauthenticated attacker to upload, read, and delete files. | |||||
CVE-2020-25176 | 3 Rockwellautomation, Schneider-electric, Xylem | 31 Aadvance Controller, Isagraf Free Runtime, Isagraf Runtime and 28 more | 2024-11-21 | 9.3 HIGH | 9.1 CRITICAL |
Some commands used by the Rockwell Automation ISaGRAF Runtime Versions 4.x and 5.x eXchange Layer (IXL) protocol perform various file operations in the file system. Since the parameter pointing to the file name is not checked for reserved characters, it is possible for a remote, unauthenticated attacker to traverse an application’s directory, which could lead to remote code execution. | |||||
CVE-2020-14516 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2024-11-21 | 7.5 HIGH | 10.0 CRITICAL |
In Rockwell Automation FactoryTalk Services Platform Versions 6.10.00 and 6.11.00, there is an issue with the implementation of the SHA-256 hashing algorithm with FactoryTalk Services Platform that prevents the user password from being hashed properly. | |||||
CVE-2020-13573 | 1 Rockwellautomation | 1 Rslinx | 2024-11-21 | 5.0 MEDIUM | 7.5 HIGH |
A denial-of-service vulnerability exists in the Ethernet/IP server functionality of Rockwell Automation RSLinx Classic 2.57.00.14 CPR 9 SR 3. A specially crafted network request can lead to a denial of service. An attacker can send a sequence of malicious packets to trigger this vulnerability. | |||||
CVE-2020-12038 | 1 Rockwellautomation | 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more | 2024-11-21 | 4.3 MEDIUM | 5.5 MEDIUM |
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable. A memory corruption vulnerability exists in the algorithm that matches square brackets in the EDS subsystem. This may allow an attacker to craft specialized EDS files to crash the EDSParser COM object, leading to denial-of-service conditions. | |||||
CVE-2020-12034 | 1 Rockwellautomation | 5 Eds Subsystem, Rslinx, Rslinx Enterprise and 2 more | 2024-11-21 | 4.8 MEDIUM | 8.2 HIGH |
Products that use EDS Subsystem: Version 28.0.1 and prior (FactoryTalk Linx software (Previously called RSLinx Enterprise): Versions 6.00, 6.10, and 6.11, RSLinx Classic: Version 4.11.00 and prior, RSNetWorx software: Version 28.00.00 and prior, Studio 5000 Logix Designer software: Version 32 and prior) is vulnerable.The EDS subsystem does not provide adequate input sanitation, which may allow an attacker to craft specialized EDS files to inject SQL queries and manipulate the database storing the EDS files. This can lead to denial-of-service conditions. | |||||
CVE-2020-12033 | 1 Rockwellautomation | 1 Factorytalk Services Platform | 2024-11-21 | 5.8 MEDIUM | 8.8 HIGH |
In Rockwell Automation FactoryTalk Services Platform, all versions, the redundancy host service (RdcyHost.exe) does not validate supplied identifiers, which could allow an unauthenticated, adjacent attacker to execute remote COM objects with elevated privileges. | |||||
CVE-2020-12031 | 1 Rockwellautomation | 1 Factorytalk View | 2024-11-21 | 4.6 MEDIUM | 7.5 HIGH |
In all versions of FactoryTalk View SE, after bypassing memory corruption mechanisms found in the operating system, a local, authenticated attacker may corrupt the associated memory space allowing for arbitrary code execution. Rockwell Automation recommends applying patch 1126290. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx. | |||||
CVE-2020-12029 | 1 Rockwellautomation | 1 Factorytalk View | 2024-11-21 | 6.8 MEDIUM | 9.0 CRITICAL |
All versions of FactoryTalk View SE do not properly validate input of filenames within a project directory. A remote, unauthenticated attacker may be able to execute a crafted file on a remote endpoint that may result in remote code execution (RCE). Rockwell Automation recommends applying patch 1126289. Before installing this patch, the patch rollup dated 06 Apr 2020 or later MUST be applied. 1066644 – Patch Roll-up for CPR9 SRx. | |||||
CVE-2020-12028 | 1 Rockwellautomation | 1 Factorytalk View | 2024-11-21 | 5.5 MEDIUM | 7.3 HIGH |
In all versions of FactoryTalk View SEA remote, an authenticated attacker may be able to utilize certain handlers to interact with the data on the remote endpoint since those handlers do not enforce appropriate permissions. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs. | |||||
CVE-2020-12027 | 1 Rockwellautomation | 1 Factorytalk View | 2024-11-21 | 4.0 MEDIUM | 4.3 MEDIUM |
All versions of FactoryTalk View SE disclose the hostnames and file paths for certain files within the system. A remote, authenticated attacker may be able to leverage this information for reconnaissance efforts. Rockwell Automation recommends enabling built in security features found within FactoryTalk View SE. Users should follow guidance found in knowledge base articles 109056 and 1126943 to set up IPSec and/or HTTPs. |