Vulnerabilities (CVE)

Filtered by vendor Rockwellautomation Subscribe
Filtered by product Compact Guardlogix 5380 Firmware
Total 3 CVE
CVE Vendors Products Updated CVSS v2 CVSS v3
CVE-2022-3157 1 Rockwellautomation 12 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 9 more 2024-02-04 N/A 7.5 HIGH
A vulnerability exists in the Rockwell Automation controllers that allows a malformed CIP request to cause a major non-recoverable fault (MNRF) and a denial-of-service condition (DOS).
CVE-2022-1161 1 Rockwellautomation 48 Compact Guardlogix 5370, Compact Guardlogix 5370 Firmware, Compact Guardlogix 5380 and 45 more 2024-02-04 7.5 HIGH 9.8 CRITICAL
An attacker with the ability to modify a user program may change user program code on some ControlLogix, CompactLogix, and GuardLogix Control systems. Studio 5000 Logix Designer writes user-readable program code to a separate location than the executed compiled code, allowing an attacker to change one and not the other.
CVE-2022-1159 1 Rockwellautomation 10 Compact Guardlogix 5380, Compact Guardlogix 5380 Firmware, Compactlogix 5380 and 7 more 2024-02-04 6.5 MEDIUM 7.2 HIGH
Rockwell Automation Studio 5000 Logix Designer (all versions) are vulnerable when an attacker who achieves administrator access on a workstation running Studio 5000 Logix Designer could inject controller code undetectable to a user.