Total
8 CVE
CVE | Vendors | Products | Updated | CVSS v2 | CVSS v3 |
---|---|---|---|---|---|
CVE-2017-7903 | 1 Rockwellautomation | 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
A Weak Password Requirements issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected products use a numeric password with a small maximum character size for the password. | |||||
CVE-2017-7902 | 1 Rockwellautomation | 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
A "Reusing a Nonce, Key Pair in Encryption" issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. The affected product reuses nonces, which may allow an attacker to capture and replay a valid request until the nonce is changed. | |||||
CVE-2017-7901 | 1 Rockwellautomation | 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more | 2024-11-21 | 9.0 HIGH | 8.6 HIGH |
A Predictable Value Range from Previous Values issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. Insufficiently random TCP initial sequence numbers are generated, which may allow an attacker to predict the numbers from previous values. This may allow an attacker to spoof or disrupt TCP connections, resulting in a denial of service for the target device. | |||||
CVE-2017-7899 | 1 Rockwellautomation | 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
An Information Exposure issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. User credentials are sent to the web server using the HTTP GET method, which may result in the credentials being logged. This could make user credentials available for unauthorized retrieval. | |||||
CVE-2017-7898 | 1 Rockwellautomation | 21 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 18 more | 2024-11-21 | 5.0 MEDIUM | 9.8 CRITICAL |
An Improper Restriction of Excessive Authentication Attempts issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 programmable-logic controllers 1763-L16AWA, Series A and B, Version 16.00 and prior versions; 1763-L16BBB, Series A and B, Version 16.00 and prior versions; 1763-L16BWA, Series A and B, Version 16.00 and prior versions; and 1763-L16DWD, Series A and B, Version 16.00 and prior versions and Allen-Bradley MicroLogix 1400 programmable logic controllers 1766-L32AWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWA, Series A and B, Version 16.00 and prior versions; 1766-L32BWAA, Series A and B, Version 16.00 and prior versions; 1766-L32BXB, Series A and B, Version 16.00 and prior versions; 1766-L32BXBA, Series A and B, Version 16.00 and prior versions; and 1766-L32AWAA, Series A and B, Version 16.00 and prior versions. There are no penalties for repeatedly entering incorrect passwords. | |||||
CVE-2016-9338 | 1 Rockwellautomation | 20 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 17 more | 2024-11-21 | 4.0 MEDIUM | 2.7 LOW |
An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. Because of an Incorrect Permission Assignment for Critical Resource, users with administrator privileges may be able to remove all administrative users requiring a factory reset to restore ancillary web server function. Exploitation of this vulnerability will still allow the affected device to function in its capacity as a controller. | |||||
CVE-2016-9334 | 1 Rockwellautomation | 20 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 17 more | 2024-11-21 | 5.0 MEDIUM | 7.3 HIGH |
An issue was discovered in Rockwell Automation Allen-Bradley MicroLogix 1100 controller 1763-L16AWA, Series A and B, Version 14.000 and prior versions; 1763-L16BBB, Series A and B, Version 14.000 and prior versions; 1763-L16BWA, Series A and B, Version 14.000 and prior versions; and 1763-L16DWD, Series A and B, Version 14.000 and prior versions. User credentials are sent to the web server in clear text, which may allow an attacker to discover the credentials if they are able to observe traffic between the web browser and the server. | |||||
CVE-2016-0868 | 1 Rockwellautomation | 9 1763-l16awa Series A, 1763-l16awa Series B, 1763-l16bbb Series A and 6 more | 2024-11-21 | 10.0 HIGH | 9.8 CRITICAL |
Stack-based buffer overflow on Rockwell Automation Allen-Bradley MicroLogix 1100 devices A through 15.000 and B before 15.002 allows remote attackers to execute arbitrary code via a crafted web request. |