CVE-2020-14483

A timeout during a TLS handshake can result in the connection failing to terminate. This can result in a Niagara thread hanging and requires a manual restart of Niagara (Versions 4.6.96.28, 4.7.109.20, 4.7.110.32, 4.8.0.110) and Niagara Enterprise Security (Versions 2.4.31, 2.4.45, 4.8.0.35) to correct.
References
Link Resource
https://us-cert.cisa.gov/ics/advisories/icsa-20-224-03 Third Party Advisory US Government Resource
Configurations

Configuration 1 (hide)

OR cpe:2.3:a:tridium:niagara:4.6.96.28:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara:4.7.109.20:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara:4.7.110.32:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara:4.8.0.110:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara_enterprise_security:2.4.31:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara_enterprise_security:2.4.45:*:*:*:*:*:*:*
cpe:2.3:a:tridium:niagara_enterprise_security:4.8.0.35:*:*:*:*:*:*:*

History

No history.

Information

Published : 2020-08-13 15:15

Updated : 2024-02-04 21:00


NVD link : CVE-2020-14483

Mitre link : CVE-2020-14483

CVE.ORG link : CVE-2020-14483


JSON object : View

Products Affected

tridium

  • niagara_enterprise_security
  • niagara
CWE
NVD-CWE-Other CWE-1088

Synchronous Access of Remote Resource without Timeout